Dual Relay Controller with Dual EDSaP Comms, AC-powered.


  • Two Relay Outputs (240V AC - 5A) can be independantly controlled from a LightSpace® EDSaP device directly connected to the unit or remotely.

  • Connects directly to an LSM, a LightSpace® Controller (LSC) via Ethernet, or through a ZigBee radio module.

  • The unit can be powered from 100V to 277V AC.

  • The output can follow the EDSaP LightSpace Manager input as a result of a user induced light level change, a motion event, or an EDSaP outdoor light sensor LSM, a IR remote control or a remote server when connected to an LSC.

  • The functionality is programmable on the device via an EDSaP to USB adapter and an application program running on a laptop.

  • Events can be logged by a server via LSC and actions taken by the rule engine of the LightSpace Server.

  • Each Relay has a programmable timeout counter associated with it so that machinery and lighting devices can be automatically turned off. The timeouts are triggered by the switch-input event associated with the relay, an LSM Motion, or LightLevel event or a remote trigger event from the server or a directly connected ZigBEE module.



LightSpace® 1665 Two Relay Controller 1/2in NPT mount

EDSaP Relay Actuator, (2) 120/240VAC Single Pole Relays, EDSaP Comms Ports, with integrated all voltage power supply.

Connects to Ringdale EDSaP motion activated sensors, daylight sensor, IR transceivers, ZigBEE radio modules and LSC Lightspace® controllers.

This device forms an integral part of the LightSpace® Building Automation System when it comes to providing energy savings without a larger building automation system or interfacing to legacy devices that are not EDSaP compliant.

The 1665 Relay Controller is the device that can turn legacy devices or non-EDSaP compliant devices ON or OFF.

LightSpace® devices are built for maximum flexibility, performance, low-power consumption.

The Relay Controller can be triggered and controlled by a multitude of LSMs and EDSaP compliant devices:

  • Analog Feel Rotary EDSaP Dimmer LSM
  • Digital Display 3 Button EDSaP Dimmer LSM
  • Digital Display 3 Button EDSaP Dimmer & Motion Sensor LSM
  • Digital Ceiling Mount EDSaP IR Dimmer & Motion Sensor LSM
  • Digital Display 3 Button EDSaP Daylight Sensor LSM

Other devices that can directly connect to the Relay Controller for applications like fan control, air conditioning control and those we have not thought of:

  • EDSaP Temperature Sensor
  • EDSaP Voltage Sensor
  • EDSaP to USB Dongle

For more information on the Ringdale LightSpace® Building Automation system www.ringdale.com/lightspace/.

Ringdale is in business for more than 30 years and deisgns and manufactures its devices within an audited ISO9000 quality system since 1986, certificate FM1880.

Part Number: 00-27-0665-0000


Technical Information

Power Supply:• 100-277V AC.• 48V DC (nominal)
Power Factor and THD:PF: >0.90 (100..277V).THD: <20%, typical <10%
Power Consumption:Max: 3 Watts

Standby: 0.5 Watt no external devices connected
EDSaP Communication:COM-1 and COM-2 ports, unit repeats
Relay Outputs:2 x Un-serviceable Relays: Single Pole - Normally Open
5A / 250V (derate for DC operation)
Relay outputs are potential free
DO NOT OPERATE ABOVE 300V AC

Caution! All specifications published herein are subject to change without notice. See website ActiveLED.com for Terms and Conditions of use of the website and the information provided herein. See Ringdale website on www.ringdale-technology.com for Terms and Condtions of Sale and Service.

+1-833-850-7097